Three Phase oil immersed Earthing Grounding Transformer with conservator
100kva
20kv /0.4kv
HV&LV winding material: Copper
100kva
20kv /0.4kv
HV&LV winding material: Copper
Three Phase oil immersed Earthing Transformer with conservator
Product Description
Grounding Transformers are designed to provide an artificial, neutral point for ungrounded three phase power systems.
During the line-to-ground faults, grounding transformers provide an easy path to ground faults, thus limit the fault currents and transient over-voltages.
Grounding transformers normally carry short-circuit ground current until the circuit breaker clears the fault. Therefore, they have short time ratings.
The kVA rating of a earthing transformer depends on the normal line-to-neutral voltage and the fault current value for a specified time, such as seconds to minutes.
Voltage | Up to 22kV |
Operating Voltage | 20kV |
Standard | IEC 60076-6 or Equivalent |
Rated Neutral current | |
Power rating | 100kVA |
Voltage Rating HV/LV | 20/0.4kV |
Cooling methods | ONAN |
Frequency | 50 Hz |
Installation | Outdoor |
Zero sequence impedance | 19 Ohm |
No phase | 3 |
Voltage regulation range (No of Taps) | 5 |
Temperature rise for the windings | As per IEC standard |
Winding material | Copper |
Insulation level | According to the rated voltage (IEC70076-3) |
Impedance Voltage | 5.5 % |
Ambient temperature | -40 to +40 °C, other temperatures on request |
Vector group | ZNyn11 |
Voltage regulation Range (No.of Taps) | 5 |
Bushing | porcelain |
Creepage | 31mm/kV |
Breather | Silica gel |
Please take a brief moment and use the "Check List" below to gather the following (13) basic pieces of Grounding Transformer information:
- Winding configuration; either Zig Zag or Two Winding.
- Voltage(s) and BIL; The line-to-line value of the system to which the grounding transformer is to be connected. If a two winding grounding transformer is required, the secondary voltage must be provided as well.
- Continuous neutral current.
- System available neutral fault current and duration; example 500 amps for 10 seconds, 4000 amps for 2 seconds.
- Zero Sequence impedance percentage.
- Per phase impedance in Ohms.
- Per phase resistance in Ohms.
- X/R ratio; typically a value > 4.0.
- Special application conditions; i.e. 2000 MASL, etc.
- Enclosure construction or NEMA designation preference; i.e. high security compartmentalized padmounted, standard ventilated or substation design, special paint color, etc.
- Terminal connectivity preference; i.e. dead front, live front, conventional terminals, etc.
- Winding material; CU if not specified.
- Transformer temperature rise; 150° C if not specified.