Three Phase oil immersed Earthing Grounding Transformer with conservator 

100kva 

20kv /0.4kv 
HV&LV winding material: Copper

Three Phase oil immersed Earthing Transformer with conservator

Back to product >>
Cooperation Consulting >>

Product Details

Product Description

Grounding Transformers are designed to provide an artificial, neutral point for ungrounded three phase power systems.

During the line-to-ground faults, grounding transformers provide an easy path to ground faults, thus limit the fault currents and transient over-voltages.

Grounding transformers normally carry short-circuit ground current until the circuit breaker clears the fault. Therefore, they have short time ratings.

The kVA rating of a earthing transformer depends on the normal line-to-neutral voltage and the fault current value for a specified time, such as seconds to minutes.

Voltage Up to 22kV
Operating Voltage 20kV
Standard IEC 60076-6 or Equivalent
Rated Neutral current  
Power rating 100kVA
Voltage Rating HV/LV 20/0.4kV
Cooling methods ONAN
Frequency 50 Hz
Installation Outdoor
Zero sequence impedance 19 Ohm
No phase 3
Voltage regulation range (No of Taps) 5
Temperature rise for the windings As per IEC standard
Winding material Copper
Insulation level According to the rated voltage
(IEC70076-3)
Impedance Voltage 5.5 %
Ambient temperature -40 to +40 °C, other temperatures on
request
Vector group ZNyn11
Voltage regulation Range (No.of Taps) 5
Bushing porcelain
Creepage 31mm/kV
Breather Silica gel


100kVA 20kv 0.4kv Earthing Transformer Grounding Transformers

Please take a brief moment and use the "Check List" below to gather the following (13) basic pieces of Grounding Transformer information:

 

  1. Winding configuration; either Zig Zag or Two Winding.
  2. Voltage(s) and BIL; The line-to-line value of the system to which the grounding transformer is to be connected. If a two winding grounding transformer is required, the secondary voltage must be provided as well.
  3. Continuous neutral current.
  4. System available neutral fault current and duration; example 500 amps for 10 seconds, 4000 amps for 2 seconds.
  5. Zero Sequence impedance percentage.
  6. Per phase impedance in Ohms.
  7. Per phase resistance in Ohms.
  8. X/R ratio; typically a value > 4.0.
  9. Special application conditions; i.e. 2000 MASL, etc.
  10. Enclosure construction or NEMA designation preference; i.e. high security compartmentalized padmounted, standard ventilated or substation design, special paint color, etc.
  11. Terminal connectivity preference; i.e. dead front, live front, conventional terminals, etc.
  12. Winding material; CU if not specified.
  13. Transformer temperature rise; 150° C if not specified.