Reference technical data sheet of electrolyzed electro-chemistry rectifier transformer

  1. Main technical parameters
No. Technical item technical requirement
1 load Parallel connection of a set of rectifier equipment
2 Insulation level Comply with national standards
3 Equipment type Indoor type
4 Altitude ≤1000m
5 Cooling form Oil immersed ONAN
6 Voltage combination 110 ±2*2.5%/ 0.740*2 KV
7 Voltage regulation rate 110KV / ±2*2.5%
8 insulation resistance Comply with national standards
9 Voltage resistance of the primary and secondary sides of the wire bundle Comply with national standards (secondary side withstand voltage 7600V)
10 Rated capacity (KVA) 90MVA
11 Phase number three
12 Rated frequency 50Hz
13 Connection group Y+7.5 y6 d5 / Y-7.5 y6 d5
14 Short-circuit impedance 7.5%
15 Total loss ≤1.2 %
16 ambient temperature -15ºC-40ºC
17 temperature rise According to the national standard (top oil temperature rise of self cooled oil immersed transformer ≤ 60K).
Winding temperature rise ≤ 65K)
18 Paint color, surface treatment RAL7033,WET PAINTING 120um
19 Decoupling factor Decoupling factor of two independent windings on the secondary side > 0.8
20 Valve side outlet sequence a1 b1 c1; a2 b2 c2
21 Cable wiring box Stainless steel material, protection level IP54
22 other The rectifier transformer is equipped with a trolley at the bottom, which can be moved in four directions with rail distance of 1475mm.
23 other Separate isolation of primary and secondary windings,  with shielding and reliable grounding between the primary and secondary windings
24 General requirements 1. The transformer can only be manufactured after we confirm  outline drawing and wiring diagram.
2. Equipment should be equipped with corresponding nameplates or safety warning labels.
3. The appearance surface is flat, without collision marks, welding without spatter, false welding, undercut, and uniform paint thickness.
25 Documents while delivery The delivery documents include but are not limited to the following documents:
Product Manual, Use and Maintenance Manual, Test Report, Important Component Test Report or Certificate of Conformity
26 spare parts
  1. Spare oil, 5% required for each unit
  2. Sealing gasket, one for each specification except for the sealing gasket along the box edge