18000kvar Arc Furnace Oil Immersed Reactor Iron Core Series Oil Immmersed Reactor, Power Reactor-1684391801467324

18000kvar Arc Furnace Oil Immersed Reactor Iron Core Series Oil Immmersed Reactor, Power Reactor-1684391801467324

Back to product >>
Cooperation Consulting >>

Product Details

 

Series Reactors are used in Electric Arc Furnaces (EAF) to provide furnace operation with longer arcs, lower currents and lower electrode consumption. Such reactors are very useful in the first melting period. With the molten scrap, the absence of the series reactor would allow higher power transfer to the EAF, reducing the tap-to-tap cycle, thus increasing productivity.

 

This paper proposes an active series reactor based on static power converters, which has the flexibility to dynamically change its impedance value during the steel production period. Simulation of a real plant demonstrate the effectiveness of the proposition. Through-put rating up to 160 MVAr

 

Model NO.: XKSSP-18000/33

Cooling Method: Oil-immersed Type Transformer

Winding Type: Multi-winding Transformer

 

BASIC INFO.

Model NO. XKSSP-18000/33 Shape of Core Ring
Cooling Method Oil-immersed Type Transformer Brand Ville
Winding Type Multi-winding Transformer Transport Package Wooden Case
Certification ISO9001-2000, ISO9001 Specification IEC
Usage Series Furnace Reactors Trademark Ville
Frequency Characteristics High Frequency Origin China
Production Capacity 50000 Sets/Year HS Code 85

2 (26)

1 (28)

TECHNICAL PARAMETERS

1.1.1 GENERAL TECHNICAL DATA  
Highest voltage      36kV 50Hz
Operating voltage   33 kV±5% 50Hz
Voltage for aux. drivers    380V 50Hz
Control voltage     220V 50Hz
Interlock voltage   220V 50Hz
PLC signals       24V DC
Ambient temperature max./min. 45 / - 10 Deg. C
Altitude 1500 m
Humidity 80 %
1.1.2 TRANSFORMER DATA   
Operating voltage   33kV±5%
Frequency    50Hz  ±1%
Operation     Continuously
EAF transformer rated capacity     MVA (+ 20% Overload)
Rated current      2449.4 A    (+ 20% Overload)
Reactor Rated Power 18 MAVR  (25.92 MVA Overload)
Reactance in normal tap 1 Ω
Number and ratio of taps  6 taps:
100%-80%-60%-40%-20%-0
Insulation level
Winding:
Um:
AC:
BIL:
Full insulation
HV         
52 kV       
95 kV       
250 kV      
Protection level        IP54
Vector group          III 
System short circuit capacity    1500 MVA
Short circuit duration 6 sec
Short circuit times 2.5 times
Regulation method  Off circuit
Type of tap changer           NLTC  Off -circuit  motor drive
Manufacturer             Shanghai Huaming / China (ZUNYI)
Model       2*ZWL III-1600/40- 6 taps
Number of taps 6
Reactor Winding Materials Copper