Bwr series WTI covers with outside mounted current converter,but III model is with inside mounted current converter.
BWR-04 transformer winding temperature indicators thermometer,
Working temperature:-40℃~55℃
Measuring range:0℃~150℃ or upon the customer's requirement
Accuracy:±2%
Control capability:
(1)Adjustable range:full span
(2)Setting accuracy:±2℃
(3)Switch differential:6℃±2℃
(4)Rated power:AC250/15A
(5)4 switches standard setting point:K1=55℃ K2=75℃ K3=90℃ K4=130℃
Noted:The switch quantity & setting point can be made according to the customoers' requirement,and it comes with max.6 switches.
Output singals:
(1) without DC power 4-20mA
(2)Pt100(model A)
(3)with DC power 4-20mA(model D)
(4)DC 0-5V(modelE)
Bulb sensor dimension:dia14x115
Connection:M27X2 or upon the customers' requirement
Protection class:IP55
Current Converter main data:
Working temperature:-40℃~55℃
Input:0.6A~5A,output 0.5A~1.75A
Protection class:IP55