Control Render Error!ControlType:productSlideBind,StyleName:Style1,ColorName:Item0,Message:InitError, ControlType:productSlideBind Error:未将对象引用设置到对象的实例。

High Quality Combined Underground Transformer

Back to product >>
Cooperation Consulting >>

Product Details

Basic Info.

Usage:Combined Transformer, Power Transformer, Distribution Transformer

Frequency Characteristics:Power Frequency

Shape of Core:Ring

Transport Package:1PC in 1 Wooden Box

Specification:Pallet dimension 110x110x210

Origin:China

HS Code:8504339000

Production Capacity:1000PCS/Month

 

Production Description


The underground transformer can be installed in the pit below the outdoor ground level to avoid direct contact with the public. The product adopts full insulation structure to ensure personal safety. The tank adopts a fully sealed structure, which can resist flood disasters and effectively improve the reliability of the power supply system. It does not occupy the ground surface area after installation, which can be harmonious with the environment, and also meets with the high waterproof requirement of underground power grids.

 

Product Features

  1. Suitable for urban environment (installed in basement or cellar), especially suitable for densely populated central cities.
  2. Suitable for lighting systems and power systems for streets, highways, bridges, tunnels, parking lots, airports, seaports, tourist attractions, etc.
  3. Both high and low-voltage terminals are fully insulated ,waterproof and shielded.
  4. The enclosure is made of anticorrosive steel plate or stainless steel plate, fully sealed and submerged in water for a period of time.
  5. The protection system fully considers the convenience and safety, the accessories from American COOPER company or adopt high-quality Chinese products with the same performance.
  6. The underground transformer is operated by the operating rod, which has the same operation mode as the combined transformer.
  7. Fully consider the particularity of heat dissipation conditions, the underground transformer adopts low loss and low temperature design.
  8. The transformer cellar is equipped with a protection device to prevent water from entering and an automatic drainage device.
  9.  
Product Features

foundation.

  1. Pit foundation: pre-compression molding with steel plates above 6mm and fully sealed structure can be used to ensure that surface water and other debris cannot enter the pit, also can adopt prefabricated reinforced concrete structure, and advanced waterproof technology is used to ensure that the foundation does not leak.
  2. A sump is set at the bottom of the pit, and a submersible pump controlled by the automatic drainage system is installed.
  3. High and low voltage cable mounting brackets are installed in the pit to facilitate cable installation and fixation.
  4. Fireproof lights are installed in the pit for easy maintenance.
  5. The top cover of the foundation is provided with an openable inspection hole.
  6. A fan is installed between the ground power distribution cabinet and the foundation pit, so that the pit and the outside air can be interchanged. When the temperature rise of the underground combined transformer reaches the set value, the fan will automatically start to perform forced air exhaust to ensure the normal operation of the transformer and high and low voltage switchgear.

 

Underground transformer

  1. The cabinet is made of stainless steel, fully sealed, and has a protection level IP68, can be immersed in water for operation.
  2. Both high and low-voltage terminals are fully insulated ,waterproof and shielded which makes the operation safer.
  3. Use naphthenic transformer oil to ensure good heat dissipation capacity.
  4. Adopt low loss value design, energy saving effect is remarkable.
  5. High insulation and heat resistance capacity, environmentally friendly.
  6. Back-up and plug-in fuse, to give the transformer safer protection.
  7. The load switch has two, three, and four positions and is suitable for a variety of power supply systems.
ain Technical Parameters of Underground Transformers

 

Rated capacity
(KVA)
No-load loss
W
Load loss
(75°) W
No-load current
(%)
Impedance Voltage (%)
30 91 600 0.63 4
50 119 870 0.60
63 140 1040 0.57
80 168 1250 0.54
100 203 1500 0.48
125 238 1800 0.45
160 280 2200 0.42
200 336 2600 0.39
250 392 3050 0.36
315 469 3650 0.33
400 560 4300 0.30
500 672 5100 0.30
630 810 6200 0.27 4.5
800 980 7500 0.24
1000 1150 10300 0.21
1250 1360 12000 0.18
1600 1640 14500 0.18
2000 1960 17820 0.30
2500 2310 20700 0.25 5.5

 

Test and Inspection Equipments