GGJ low-voltage reactive power intelligent compensation device
Overview
GGJ low-voltage reactive power intelligent compensation device adopts computer-aided design (CAD), introduces microcomputer control, implements intelligent tracking compensation for reactive power, its structure is reasonable, technology first, widely used in low-voltage power grid, improve power factor, reduce reactive power loss, improve power supply quality, is a new generation of energy-saving products. Dedicated for reactive power compensation of 130-600kva three-phase transformers.
Model Meaning
use
Altitude: w 2000m;
♦ Ambient temperature:-20 bar ~ + 45C;
♦ Relative humidity: W90% at 20C;
Installation environment: no harmful gas and steam, no conductive or explosive dust particles and serious mold.
Key Features
♦ Using intelligent controller control, complete functions, reliable performance, automatic compensation method: the power factor can be increased to more than 0.9:
♦ Real-time display of grid power factor, display range: lag (0.00-0.99), lead (0.00-0.99):
with overvoltage, harmonic, compensation, system failure, lack of phase, overload and other comprehensive protection functions;
♦ Memorize the set parameters, the system will not lose the parameters after power failure, and the power grid will automatically enter the running state after returning to normal, without personnel on duty:
♦ According to the power grid load balance situation, take separate phase compensation or mixed compensation;
♦ Strong anti-interference ability, can resist the amplitude of 2000V interference pulse directly input from the power grid, which is higher than the national professional standard.
Main technical parameters
Rated voltage: 0.38-0.66kV;
Rated frequency: 50Hz;
♦ Rated capacity: 1-600kvar;
Applicable voltage range:( 0.85-1.1) times rated voltage;
♦ Maximum allowable current: 1.3 times the rated current;
Control loop: 1-16 loop;
♦ Cutting time: 1-15 times, adjustable;
♦ Working mode: automatic, continuous operation.
Distribution network detection function
Measure and record the three-phase voltage, current, frequency, active power, reactive power, power factor, active power and reactive power of the low-voltage side of the transformer in real time: the total distortion rate of voltage and current and the 2-25 harmonic content;
♦ With RS-232 and RS-485 interface, it can transcribe data on a handheld computer, and can also realize wireless meter reading, device testing, parameter setting, real-time measurement data and record data reading through remote communication functions;
Data analysis function: it can analyze and process operating load data and make statistical inquiries. Comprehensive analysis of power supply quality, calculation of voltage qualification rate, power supply load rate, reliability rate and maximum load rate; Query power factor, active power and reactive power in time periods; Draw graphs of voltage, current and power factor of each phase: print comprehensive analysis and statistics.
Dimensions and Installation
Device System Principle Example
Ordering Instructions
1. Main circuit scheme diagram; 2. Compensation capacity and compensation method; 3. If it is inconsistent with the normal use conditions of the product, it shall be explained in advance.