控件[tem_25_34]渲染出错,Source:未将对象引用设置到对象的实例。
In electric arc furnaces, which use long arcs and high values of secondary voltage, it is often helpful to introduce an additional reactor
with the purpose of:

Arc stability and power regulation
Optimisation electrodes consumption
Limitation of current during smelting process
Reduction of flicker on the feeding network.

Electric Arc Furnace Serial Furnace Reactor 30mva Three Phase Oil Immersed Iron Core Serial Reactor

Back to product >>
Cooperation Consulting >>

Product Details

Model NO. XKSSP-35000/33
Trademark VILLE
HS Code 85

 

Specification As per drawing                         
Origin China
Production Capacity 5000pieces/Year

 

 

Product Description
Specialized in the design and construction of industrial transformers

Product Description
Specialized in the design and construction of industrial transformers
*• Through-put rating up to 150 MVAr
In electric arc furnaces, which use long arcs and high values of secondary voltage, it is often helpful to introduce an additional reactor
with the purpose of:

Arc stability and power regulation
Optimisation electrodes consumption
Limitation of current during smelting process
Reduction of flicker on the feeding network.
The reactors are series connected with the furnace transformers and have some regulation taps (for the reactance regulation) operated
with either an onload tap changer (OLTC), for maximum flexibility, or with a de-energized tap changer (DETC). 

The reactor can be assembled:
Inside the main transformer tank
Entirely separated from the transformer
Located next to the transformer (On Board Reactor).
In the OBR (On Board Reactor) solution, the reactor and the transformer are  linked by a removable cable duct.
Extends equipment lifecycle due to reduced unstable arc furnace currents
High mechanical strength withstands elevated forces caused by elevated switching currents
Tap adjustment is possible
Inductance of the reactor is frequently variable and requires large adjustment steps
Conservative temperature rise ensures extended service life
Surface treatment protects against UV radiation and pollution
Environmentally friendly
Maintenance-free design

 

 

  • Auxillary voltage for power circuits 220 Vac, 50 Hz , 3 phase
    Control Voltage 24 Vdc
    Nominal Voltage 34.5 KV 50 Hz, 3 phase
    Rated capacity 51.840 MVAr
    Rated current 2400 A
    X ( Ω/phase )
    Insulation level ( 1U,1V,1W ) 95/250 KV BIL
    Vector Group iii
Maximum allowable temperature rise for oil 60 K
Maximum allowable temperature rise for winding 65 K
Number of positions  7 ( pos1: 0 Ω, po2: 0.5 Ω, pos3: 1Ω , pos4: 1.5 Ω, pos5: 2 Ω, pos6: 2.5 Ω, 
pos7: 3 Ω,
Tap changer mechanism On-load tap changer, MR brand
Oil filter equipment for OLTC All diverter switch compartments oil will be circulated through a filter circuit 
equipped with filter clogged electrical signal.
Shell and tube heat exchangers double wall type, quantity two , each with %100 cooling capacity. Inlet water 
temperature: 35 C. 2 oil circulation pumps. Temperature and flow indicators 
both for oil and water circuits
Reactor condition monitoring Oil level indicators for expansion tanks, oil and winding temparature indicators.
Reactor protection Bucholz relay with relevant alarm and trip contact connections. Pressure relief 
valve for tank over pressure protection, equipped with trip contact.

 

 