控件[tem_25_34]渲染出错,Source:未将对象引用设置到对象的实例。
AUTOTRANSFORMER 150/165 MVA, 330/132/ 33 KV
Type:Oil immersed with On load Tap-changer, 3 phase ;
Installation :Outdoor in Switchyard
Rated Power:
Primary / Secondary:150/165MVA
Tertiary:36MVA
Rated Voltage: HV Winding 330kv
LV Winding 132kv
Tertiary Winding 33kv
Rated Frequency: 50HZ
Type:Oil immersed with On load Tap-changer, 3 phase ;
Installation :Outdoor in Switchyard
Rated Power:
Primary / Secondary:150/165MVA
Tertiary:36MVA
Rated Voltage: HV Winding 330kv
LV Winding 132kv
Tertiary Winding 33kv
Rated Frequency: 50HZ
330KV Auto Transformer AUTOTRANSFORMER 150/165 MVA, 330/132/ 33 KV 0SFSZ—165MVA/330kV Transformer
AUTOTRANSFORMER 150/165 MVA, 330/132/33 kV
OSFSZ-165MVA/330KV
Sr. No. | DESCRIPTION | UNIT | SPECIFICATION REQUIREMENT |
1 | Manufacturer | - | CHINA |
Country | CHINA | ||
- Class | - | A | |
- Type | Oil immersed with On load Tap-changer, 3 phase | ||
2 | Installation | Outdoor in Switchyard | |
3 | Rated Power | ||
‘ Primary / Secondary | MVA | 150/165 | |
- Tertiary | MVA | 36 | |
4 | Rated Voltage | ||
- HV Winding | kV | 330 | |
- LV Winding | kV | 132 | |
- Tertiary Winding | kV | 33 | |
5 | Rated frequency | Hz | 50 |
6 | 3 Phase Winding Connections | - | YN,a0,d11 |
(Group of Vectors IEC 76) | |||
7 | Cooling | - | ONAN/ |
ONAF | |||
8 | Tap Changer : | ||
- Make | MR GERMANY | ||
- Type | Oil / Vacuum | ||
- On-Load Tap Changer Location | HV Neutral side | ||
- Regulating range | % | +5 to -15 in 17 steps | |
- Rating | Rated power on all taps | ||
9 | Rated current at ONAF rated power and rated voltage tap: | ||
- HV Winding | A | 289 | |
- LV Winding | A | 722 | |
- Tertiary Winding | A | 630 | |
10 | No- load current through: | At 100% | |
- HV Winding | A | 1.15(max) | |
- LV Winding | A | 2.88(max) | |
- Tertiary Winding | A | 2.5(max) | |
11 | Short Circuit Impedance | Base: Rated voltage and 165 MVA |
|
12 | Direct Impedance at nominal Voltage tap: | ||
- HV / LV | % | 15 | |
- HV / TV | % | 50 | |
- LV / TV | % | 33 | |
13 | Direct Impedance at minimum voltage tap: | ||
% | ≤ 15 | ||
14 | Direct Impedance at maximum voltage tap: | ||
- HV/LV | % | 15 | |
15 | Zero sequence impedance at nominal voltage tap | % | 10.47 |
- HV / LV | % | - | |
- HV / TV | % | - | |
- LV / TV | % | - | |
16 | Tolerance to be applied to the short circuit impedance, in terms of % of the guaranteed values on: | ||
- Nominal voltage tap | % | ±5 | |
- Other taps | % | ±15 | |
17 | Transformer capacity to withstand external short circuits: | ||
Short Circuit Duration | s | 2 |